Tel:
Ningbo Tian'an Jinghua Power Technology Co., Ltd.
Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Home ProductsLow Voltage Circuit Breakers

Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947

Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947

  • Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947
Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947
Product Details:
Place of Origin: CHINA
Brand Name: TIANAN
Certification: CCC
Model Number: TANW1
Payment & Shipping Terms:
Minimum Order Quantity: 10 sets
Price: Pending
Packaging Details: Wooden case
Delivery Time: 30 work days
Payment Terms: L/C, T/T
Supply Ability: 2000sets/year
Contact Now
Detailed Product Description
Rated Voltage: 400-600V Rated Current: 630A-6300A
Environment: Indoor Warranty: 2 Years
Poles Number: 4 Pollution Degree: 3
Product Name: Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker
High Light:

6300A Low Voltage Circuit Breakers

,

600V Low Voltage Circuit Breakers

,

low tension air circuit breaker IEC 60947

Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947

 

Application range of Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947

TANW1 series intelligent universal circuit breaker (hereinafter referred to as circuit breaker) is a new generation developed by our company, adopting advanced technology. It is suitable in distribution network (4 pole is suitable in 3-phase-4-wire or 3-phase-5 wire system) with AC 50Hz, rated voltage 400, 600V, rated current 630-6300A, for distribution and protecting circuit and power unit from the faults of overload, undervoltage, short circuit, single phase ground. The circuit breaker has a function of intelligent protection, accurate selective protection, to improve power distribution reliability avoiding unnecessary outage.

 

Condition for installation, operation and transportation

1. Elevation of installation site: ≤2000m.

2. Ambient temperature: -5℃~+40℃, average temperature in 24h: up to +35℃.

3. Relative humidity: not exceeding 50% at +40℃ ambient temperature. With lower temperature, higher humidity would be permitted, but the lowest average temperature in a month not exceeding +25℃ during the most moist month, and the maximum monthly average relative humidity not exceeding 90% in that month, and giving consideration to the dews on the goods surface, which would appear due to temperature change.

4. Pollution degree: 3.

5. Work reliably in earthquake (4g) situation.

6. Deliver and storage between -25℃- +55℃.

7. The circuit breaker can be installed vertically or horizontally.

 

Parameter of Low Tension Air 6300A 600V Low Voltage Circuit Breakers Circuit Breaker IEC 60947

Type TANW1-2000 TANW1-3200 TANW1-4000 TANW1-6300
Frame rated current
Inm(A)
2000 3200 4000 6300
Rated current In(A) 630,800,
1000,1250,1600,2000
2000,2500,2900,3200 3200,3600,
4000
4000,5000,
6300
Rated insulation voltage Ui(V) 1000
Rated operational voltage Ue(V) AC400,AC690
Rated limit short circuit breaking capacity Icu(kA) AC400V 80 100 100 120
AC690V 50 65 75 85
Rated running short circuit breaking capacity Ics(kA) AC400V 50 65 80 100
AC690V 40 65 65 75
Rated short time withstand current 1cw,1s AC400V 50 65 65/80 85/100
Rated impulse withstand current Uimp(V) 8000
Dielectric property(V) 3000
Service life Total times 5000 3000 3000 2000
Electricity cycles 500 500 500 500
No electricity cycles 4500 2500 2500 1500

Contact Details
Ningbo Tian'an Jinghua Power Technology Co., Ltd.

Contact Person: admin

Tel: +8613858385873

Send your inquiry directly to us
Ningbo Tian'an Jinghua Power Technology Co., Ltd.
21/F, Building 1, No. 816,Jinghua Road, Hi-tech Zone,Ningbo, Zhejiang, P.R. China
Tel:86-574-87911488
Mobile Site Privacy Policy | China Good Quality High Voltage Switchgear Supplier. © 2021 - 2022 voltageswitchgear.com. All Rights Reserved.