Place of Origin: | CHINA |
Brand Name: | Tianan Electric |
Certification: | ISO9001,IEC |
Model Number: | FT16-40.5 |
Minimum Order Quantity: | 10sets |
---|---|
Price: | Pending |
Packaging Details: | wooden cases |
Delivery Time: | 35 work days |
Payment Terms: | L/C, T/T |
Supply Ability: | 1000sets per year |
Rated Voltage: | 40.5KV | Rated Current: | 630A |
---|---|---|---|
Fuse Rated Current: | 100A | Earthing Switch Making Currrent: | 31.5KA |
Poles Nunber: | 3 | Product Name: | Medium Voltage Fuse Combinations 40.5kv Vacuum Load Break Switch 50hz |
High Light: | Fuse Combinations 40.5KV Vacuum Load Break Switch,630A Vacuum Load Break Switch,medium voltage load break switch 50Hz |
Medium Voltage Fuse Combinations 40.5KV Vacuum Load Break Switch 50Hz
General of Medium Voltage Fuse Combinations 40.5KV Vacuum Load Break Switch 50Hz
FT16-40.5,FT16-40.5R is applied in power grid with AC 50HZ,rated voltage of 35Kv.It can be applied in breaking the load current, overload current and short-circuit current. The product is the main element of HXGT16-40.5 indoor AC metal-clad switchgear and DFT16-40.5 outdoor HV cable branch box.HXGT16 is especially designed for 35KV compact substation ,secondary small scale distribution substation.It is particularly the best choice of wind turbine generator system and power transmission grid equipment for control and protection of the transformer terminal.DTW is a transit station for power transmission cable ,used for outdoor cable line control ,contact, tap, branch or conversion.
Feature of Medium Voltage Fuse Combinations 40.5KV Vacuum Load Break Switch 50Hz
· With separate fuse compartment, and two sides of the fuse mount with earthing switch, to ensure the safety of the maintainer when changing the fuse.
· Easy change of fuse. If it is used for wind power package substation, no necessity to stop other shunt-wound wind power unit when changing the fuse.
· When the LBS fuse’s single phase burn out, the switch will trip with the action of striker, to avoid phase-deficient operation of transformer.
· LBS has evident fracture.
· LBS has manual and motor driven operations
· LBS with compact structure and small volume, the external dimension of HXGT16 with the LBS: width 1600, depth1600, height2200.
· Perfect ‘five-protection’ function
· Cable outgoing end can connect with many cables.
· Apply unique shunt connection type vacuum arc-extinguishing device, economical and practical.
Parameters of Medium Voltage Fuse Combinations 40.5KV Vacuum Load Break Switch 50Hz
S/N | Item | Unit | Data | ||||
1 | Rated voltage | kV | 40.5 | ||||
2 | Rated frequency | Hz | 50 | ||||
3 | Rated current | A | 630 | ||||
4 | Fuse Rated current | A | 100 | ||||
5 | Rated short-time Withstand Current | KA | 20 | ||||
6 |
Rated short-circuit making Current |
s | 4 | ||||
7 | KA | 50 | |||||
8 | Rated peak withstand current | KA | 50 | ||||
9 | Rated load breaking Current | A | 630 | ||||
10 | Rated Transfer (take-over)breaking current(with 100A fuses) | A | 2000 | ||||
11 | Earthing switch making current | KA | 31.5 | ||||
12 | FT16-40.5 main circuit resistance | uΩ | ≤200 | ||||
13 | FT16-40.5R Main circuit resistance (not including fuse link resistance) | uΩ | ≤400 | ||||
14 | Opening time | ms | 60-70 | ||||
15 | Fuse rated breaking current | KA | 31.5 | ||||
16 | Rated insulation level | 1min Power frequency withstand voltage |
phase to phase/ phase-to-ground | KV | 95 | ||
Fracture/isolating Fracture | 95/118 | ||||||
lightning impulse withstand voltage (peak value) |
Phase to phase/ phase-to-ground | 185 | |||||
Fracture/isolating Fracture | 185/215 | ||||||
17 | Mechanical life | Load switch | Time | 10000 | |||
Disconnector | 2000 | ||||||
Earthing switch | 2000 | ||||||
18 | Dimensions | HXGT16 | Width | mm | 1200,2000 | ||
Depth | 1600 | ||||||
Height | 1900,2000 | ||||||
DTW | Width | 1800 | |||||
Depth | 2300 | ||||||
Height | 2100 | ||||||
Contact Person: admin
Tel: +8613858385873