132kv Mobile Transformer Substation Emergency Vehicle Mounted
1. General of 132kv Mobile Transformer Substation Emergency Vehicle Mounted
We developed the prefabricated mobile substation (hereinafter named vehicle-borne substation for short) successfully by itself according to situation of international and domestic, so that fill up the blank in domestic. This substation is mainly used for replacing totally or partially for one regular substation immediately in urgent condition and recover to supply power; it can be put into operation in high load season or time to dissolve the problem of lacking supplied power capacity in one zone; in some zones where the need of electric power is rising and exceed advance electric power construction layout, the substation can be put into operation as temporary substation to dissolve lack of electric power; and also to the zone of breaking off permanent substation construction plan because of fund shortage or other reasons. Vehicle-borne substation features of convenient transport, perfect equipment, agile and reliable, save the found for takeover of land, civil work and installation of equipment at one time and improve the reliability of supplying power in electric power system.
2.Service condition of 132kv Mobile Transformer Substation Emergency Vehicle Mounted
1 Ambient condition
a. Altitude ≤ 1000m;
b. Ambient temperature
Range of temperature: -25℃~+40℃;
c. Wind speed (outdoor) ≤ 35m/s;
d. Relative humidity ≤ 90%(+25℃);
e. Installation spot
The place shall have no fire, explosion, chemical corrosion and exquisite vibration.
2 Move condition of the substation
a. Max. speed ≤ 30km/h,when road surface is flat;
b. Max. speed ≤ 10km/h, when road surface is not flat.
Note: If the above condition can’t satisfy requirements, customer can consult with manufacturer to resolve it.
3.Type designation
4.Technical parameters of 132kv Mobile Transformer Substation Emergency Vehicle Mounted
5000,6300,8000,10000,12500,16000,20000,25000.
Table 1
No. | Item | Unit | Parameter |
1 | System voltage | kV | 132 |
2 | Rated voltage | kV | 145 |
3 | Rated frequency | Hz | 50 |
4 | Rated current | A | 2000 ,1600 |
5 | Rated 1min power frequency withstand voltage | kV | 275 |
6 | Rated lightning impulse withstand voltage | kV | 650 |
7 | Rated short time withstand current | KA | 25,31.5,40 |
8 | Rated short time withstand time | s | 3 |
9 | Rated peak withstand current | kA | 63,80,100 |
Table 2
No. | Item | Unit | Parameter | ||
1 | System voltage | kV | 132 | ||
2 | Rated voltage | kV | 145 | ||
3 | Rated frequency | Hz | 50 | ||
4 | Rated current | A | 2000 | ||
5 | Rated 1min power frequency withstand voltage | kV | 275 | ||
6 | Rated lightning impulse withstand voltage | kV | 650 | ||
7 | Rated short time withstand current / time | KA/s | 40/4 | ||
8 | Rated peak withstand current | kA | 100 | ||
9 | Rated short circuit breaking current | kA | 40 | ||
10 | Rated short circuit making current | kA | 100 | ||
11 | DC component | % | 40 | ||
12 | Rated operation sequence | O 0.3s CO 180s CO | |||
13 | Opening time | ms | 35±5 | ||
14 | Closing time | ms | 105±15 | ||
15 | Breaking time | ms | ≤60 | ||
16 | Non-simultaneity between poles | Closing | ms | ≤5 | |
Opening | ms | ≤3 | |||
17 | Fracture no. of each pole | 个 | 1 | ||
18 | Mechanical endurance | Times | ≥6000 | ||
19 | Full capacity continuous breaking times | Times | ≥20 | ||
20 |
SF6 gas pressure (20℃) |
Rated value | MPa | 0.60 | |
Alarm value | MPa | 0.55 | |||
Locking value | MPa | 0.50 | |||
21 |
SF6 gas moisture content(μl/l) |
Acceptance value | PPm | ≤150 | |
Operation allowable value | PPm | ≤300 | |||
22 | SF6 yearly gas leakage rate | % | ≤0.5 | ||
23 | Total weight of each circuit breaker | kg | 2000 | ||
Table 3
Rated primary current | 150,300,500,750,1000,1500,2000 |
Rated secondary current | 5A |
Rated output capacity and accuracy level
|
See table 4 |
Table 4
Current ratio | Rated output capacity VA | Measure accuracy level | Protection accuracy level |
150/5 300/5 500/5 750/5 1000/5 1500/5 2000/5 |
20 20 30 30,40 40,50 50 50 |
0.5 0.5 0.5 0.5 0.5 0.5 0.5 |
5P20 5P20 5P20 5P20 5P20 5P20 5P20 |
Note: (1) Straight-through type bushing current transformer is attached in the circuit breaker.
No. | Item | Unit | Parameter |
1 | System voltage | kV | 132 |
2 | Rated voltage | kV | 150 |
3 | Rated frequency | Hz | 50 |
4 | Nominal discharge current | kA | 10 |
5 | DC 1mA reference voltage | kV | ≥245 |
6 | Residual voltage under lightning impulse current (peak) | kV | ≤435 |
7 | Residual voltage under operation impulse current (peak) | kV | ≤370 |
22 | Residual voltage under steep wave impulse current (peak) | kV | ≤490 |
Table 6
No. | Item | Unit | Parameter |
1 | System voltage | kV | 132 |
2 | Rated voltage | kV | 90 |
3 | Rated frequency | Hz | 50 |
4 | Nominal discharge current | kA | 1.5 |
5 | DC 1mA reference voltage | kV | ≥140 |
6 | Residual voltage under lightning impulse current (peak) | kV | ≤260 |
7 | Residual voltage under operation impulse current (peak) | kV | ≤240 |
8 | Residual voltage under steep wave impulse current (peak) | kV | / |
Table 7
No. | Item | Unit | Parameter |
1 | System voltage | kV | 11.5 |
2 | Rated voltage | kV | 12 |
3 | Rated frequency | Hz | 50 |
4 | Rated current | A | 2000,1600,1250, |
5 | Rated 1min power frequency withstand voltage | kV | 42/48 |
6 | Rated lightning impulse withstand voltage | kV | 75/85 |
7 | Rated short time withstand current | kA | 40,31.5,25 |
8 | Rated short time withstand time | s | 4 |
9 | Rated peak withstand current | kA | 100,80,63 |
10 | Rated short circuit breaking current | kA | 40,31.5,25 |
11 | Rated short circuit making current | kA | 100,80,63 |
12 | Rated operation sequence | O 0.3s CO 180s CO | |
13 | Mechanical endurance | Times | ≥10000 |