Place of Origin: | China |
Brand Name: | Tianan Power |
Certification: | ISO9001,IEC |
Model Number: | XGN49 |
Minimum Order Quantity: | 10 unit |
---|---|
Price: | Pending |
Packaging Details: | Wooden Case |
Payment Terms: | L/C, T/T |
Supply Ability: | 100 sets/year |
Rated Current: | 3150A | Protection Degree: | IP67 |
---|---|---|---|
Mechanical Lif: | 10000 Times | Operation Voltage: | High Voltage |
Shell Material:: | Aluminum Alloy | Structure: | Fixed Type |
Product Name: | C-GIS GAS Insulated Switchgear | Application: | Power Distribution And Control |
High Light: | 3150A High Voltage Switchgear,High Voltage Switchgear,Fixed sf6 gas insulated switchgear |
C-GIS GAS Insulated switchgear, 3150A, with high reliability
Technical characteristics of C-GIS GAS Insulated switchgear
Max safety
C-GIS GAS Insulated switchgear Volume minimization
Weight of switchgear:
Width (mm) | Rated current (A) | Weight of standard switchgear (estimated value) (kg) |
800 | 3150 | 1600 |
C-GIS GAS Insulated switchgear Structure of switchgear main body and devices
The HV components are sealed to each separate SF6 Gas sealing chamber, the rated gas fling pressure is 0.03Mpa, the miniature operating pressure is 0.01Mpa, the enclosure of chamber uses 3mm stainless steel to weld to each separate sealing gas chamber, The inner surface of the gas tank is welded with reinforcing bars to ensure that the deformation of the air box at high altitude is within the allowable range. Static seal using EPDM "O" ring, dynamic seal using bellows and magnetic fluid, through the above measures to ensure the very low leakage rate of the gas tank. Annual leakage rate of gas is less than 0.1%, gas tightness can be maintained for 40 years without gas supplement. The whole life cycle is 40 years, the product is maintenance-free, but has maintainable performance.
Install pressure release device in the CB chamber and busbar chamber, when rare intemal arc fault occurs in the gas chamber, the orrresponding pressure release device will work to release overpressure and protect personal safety.
HV live parts are insulated by insulating gas and enclosed in the gas chamber, which can permanenty and effectively prevent pollution, moisture, foreign matter and other harmful effects. Each cabinet is an independent unit, and the connection of its busbar is completed by plug-in busbar connection device.
Available switchgear type (primary scheme) of C-GIS GAS Insulated switchgear
It is suitable for single bus or double bus system: incoming cabinet, outgoing cabinet, feeder cabinet, bus connecting cabinet, PT cabinet, metering cabinet and so on, which can be with different connecting methods, such as parallel connection of multi cables. The typical primary scheme please refers to the attached page.
Dimension:
External dimensions for inner cone cable outgoing, Side extension bus, rated current: 3150A,
A. Circuit breaker chamber B. Disconnector bus chamber C. LV chamber
D. Cable chamber E. Gas release channel F. Gas release channel (optional)
Note: Install the cooling fan to the 3150A switchgear.
Contact Person: admin